8028 Cambridge Circle - A UNIT A
No heating, under 55℉ outside
Photos
Completed
Days open: 52
Warranty / owner-preferred contractor
Additional details
Resident said: No heating, under 55℉ outside
Emergency Selected: No heating, under 55℉ outside
Additional Details: They have came and its run okay but by 30 minutes later it gets up to 96 and would not go down
Assignment
AC Guys Heating and Cooling
Scheduled: 01/28/2026
Unit Maintenance Profile
View full unit profile
BA unit id: 339
•
PM unit id: 1363601
Unit maintenance sections are not available.
Completion
Completion date
28-Jan, 11:30 am
Completion notes
we found that one of the sequencer wires was burned out, and the sequencer itself was bad. We replaced the sequencer and added a new wire. We believe the cause of the burned wire is that the unit’s label specifies a maximum of 35 amps, but the breaker box has a 40-amp breaker—5 amps over. That could be one reason the wire overheated and burned.